Collection: Seperators

Separators remove oil, fuel, silt and grease from drainage water before it reaches a sewer, watercourse or soakaway. We stock fuel and oil separators by Klargester and Oaklands Environmental, vehicle washdown separators, grease separators and traps, and Stormshark vortex separators. The first choice is what you are treating: surface water from car parks and yards, washdown water, or kitchen waste.

Read the buying guide and questions
  • Full retention separators, Klargester, for 170 to 11,110 m² drainage areas
  • Bypass separators, Klargester and Oaklands NSB, for 1,670 to 16,670 m²
  • Vehicle washdown separators, Oaklands Washceptor, 1,000 to 10,000 litres
  • Grease traps and separators, 100 to 8,000 litres
  • Fuel and oil separators are made to BS EN 858; grease separators to BS EN 1825

Questions about seperators

Full retention or bypass separator?

Full retention separators treat all the flow and suit higher-risk sites where spills are likely, such as fuel forecourts and vehicle depots. Bypass separators treat the first, most polluted flow and let heavy storm flow pass, and suit lower-risk areas like car parks.

What is the difference between a Class 1 and a Class 2 separator?

Under BS EN 858, a Class 1 separator is designed to discharge less than 5mg of oil per litre and is used before surface water drains. Class 2 discharges less than 100mg per litre and suits less sensitive outlets, such as some foul sewers.

How is a separator sized?

By the drainage area it serves, in square metres, and the site risk. Each product title gives the area it suits. Send us the drainage layout for a free drawing take-off.